Product Detailed
CPU:STM32 CPU IO:24xDI/16xDO(relay) Communication port:built-in RS422/RS485

WECON 40 i/o plc,LX2N-40MRC-A,replace Mitsubishi's plc

 

 

Model 

LX2N-40MR-A(AC100-240V,24x 24V DI,16x relay DO)

Power specifications

Rated voltage

AC100-240V

Allowed limits

AC85-264V

Rated frequency

50/60HZ

Allowed instant

outage time

Instant outage time less than 10 ms,can continue to work.

power fuse

250V 1A

Impulse current  

Maximum 15A 5ms below/AC 100V,Maximum 5ms below/AC200V

Power consumption

Less than 20W

Sensor power

output power:DC24V  400mA

General Specifications

Environment temperature

0 ~ 55 °C

Storage temperature

-20 ~ 70°C

Relative humidity

35-85%RH

Seismic resistance(DIN rails)

Meet JIS C 0040 standards, 10-57HZ 0.035MM X,Y,Z three direction 10 times each(total 80 minute each)

Meet JIS C 0040 standards, 57-150HZ 4.9M/S2 X,Y,Z three direction,10 times each,(total 80 minute each)

Seismic resistance(install directly)

 Meet JIS C 0040 standards, 10-57HZ 0.035MM X.Y.Z three direction ,10 times each(total 80 minute each)

Meet JIS C 0040 standards, 57-150HZ 4.9M/S2 X.Y.Z three direction,10 times each( total 80 minute each)

 Impact Resistance

Meet JIS C 0040 standard(147m/S2 action time, 11ms half-sine shock pulse,in X,Y,Z three direction,3 times each)  

Noise resistance

Noise voltage 1,000VP-P noise amplitude 1ns 1 frequency 30 ~ 100HZ noise simulation experiment

Withstand Voltage

AC1500V(1 minute),meet JEM-1021 standards,between power port and earth terminal.

 Insulation resistance

DC500V insulation tester test above 5MΩ, meet JEM-1021 standards,between power port and earth terminal.

Earth connection

The third kind of earth connection(do not share one place with high voltage system) *1

Operating environment

Close corrosive,combustible gas, No large electrical conductivity dust

  RAM

Program storage: 256K

Storage for powerdown mode: 16K

 Interface

COM1:RS422(programming interface,HMI common interface)

COM2:RS485,support modbus,HMI,inverter and others device communication(optional)

CAN:use board panel to extend(optional)

 Extension module

 Support to extend

 High-speed counting

Single-phase:2-path,up to 200KHZ

AB phase mode:support 1-path AB phase

 Software counts

Counter characteristics:2-path 100k,4-path 10k,total pulse 200Khz

Working mode:support 2-path AB phase

High-speed pulse output

Support 2-path,up to 200khz,support PWM,support trapezoid

accelerate and decelerate

Software function

Interrupt:counter interrupt/native machine IO interrupt/timer interrupt;IO reflash mode:support END commands/support input output real-time refresh commands/pulse capture;Programming mode:relay symbol mode+Step ladder diagram(SFC),support interrupt mode;Real-time clock:bulit-in battery,support long-acting real-time clock running;Power save:flash permanent preservation,above ten years;User trapezoid diagram capacity:16K;

 Arithmetic speed

 Basic command:0.1 μs/command

Integer operation:14 μs/command

Instruction specifications

Shell color

Black

Shell Material

ABS Plastic

Shape Size

170×90×88mm

Package size

137*102*97mm

Net weight

0.3kg

Wet weight

0.5kg