Model | LX2N-40MR-A(AC100-240V,24x 24V DI,16x relay DO) |
Power specifications | |
Rated voltage | AC100-240V |
Allowed limits | AC85-264V |
Rated frequency | 50/60HZ |
Allowed instant outage time | Instant outage time less than 10 ms,can continue to work. |
power fuse | 250V 1A |
Impulse current | Maximum 15A 5ms below/AC 100V,Maximum 5ms below/AC200V |
Power consumption | Less than 20W |
Sensor power | output power:DC24V 400mA |
General Specifications | |
Environment temperature | 0 ~ 55 °C |
Storage temperature | -20 ~ 70°C |
Relative humidity | 35-85%RH |
Seismic resistance(DIN rails) | Meet JIS C 0040 standards, 10-57HZ 0.035MM X,Y,Z three direction 10 times each(total 80 minute each) Meet JIS C 0040 standards, 57-150HZ 4.9M/S2 X,Y,Z three direction,10 times each,(total 80 minute each) |
Seismic resistance(install directly) | Meet JIS C 0040 standards, 10-57HZ 0.035MM X.Y.Z three direction ,10 times each(total 80 minute each) Meet JIS C 0040 standards, 57-150HZ 4.9M/S2 X.Y.Z three direction,10 times each( total 80 minute each) |
Impact Resistance | Meet JIS C 0040 standard(147m/S2 action time, 11ms half-sine shock pulse,in X,Y,Z three direction,3 times each) |
Noise resistance | Noise voltage 1,000VP-P noise amplitude 1ns 1 frequency 30 ~ 100HZ noise simulation experiment |
Withstand Voltage | AC1500V(1 minute),meet JEM-1021 standards,between power port and earth terminal. |
Insulation resistance | DC500V insulation tester test above 5MΩ, meet JEM-1021 standards,between power port and earth terminal. |
Earth connection | The third kind of earth connection(do not share one place with high voltage system) *1 |
Operating environment | Close corrosive,combustible gas, No large electrical conductivity dust |
RAM | Program storage: 256K Storage for powerdown mode: 16K |
Interface | COM1:RS422(programming interface,HMI common interface) COM2:RS485,support modbus,HMI,inverter and others device communication(optional) CAN:use board panel to extend(optional) |
Extension module | Support to extend |
High-speed counting | Single-phase:2-path,up to 200KHZ AB phase mode:support 1-path AB phase |
Software counts | Counter characteristics:2-path 100k,4-path 10k,total pulse 200Khz Working mode:support 2-path AB phase |
High-speed pulse output | Support 2-path,up to 200khz,support PWM,support trapezoid accelerate and decelerate |
Software function | Interrupt:counter interrupt/native machine IO interrupt/timer interrupt;IO reflash mode:support END commands/support input output real-time refresh commands/pulse capture;Programming mode:relay symbol mode+Step ladder diagram(SFC),support interrupt mode;Real-time clock:bulit-in battery,support long-acting real-time clock running;Power save:flash permanent preservation,above ten years;User trapezoid diagram capacity:16K; |
Arithmetic speed | Basic command:0.1 μs/command Integer operation:14 μs/command |
Instruction specifications | |
Shell color | Black |
Shell Material | ABS Plastic |
Shape Size | 170×90×88mm |
Package size | 137*102*97mm |
Net weight | 0.3kg |
Wet weight | 0.5kg |